Gold Member Since 2016
Audited Supplier
Firstpower Tech. Co., Ltd.

Battery, UPS Battery, Sealed Lead Acid Battery manufacturer / supplier in China, offering LFP12110 Stationary Sealed UPS Battery, DIN Standard Traction Battery (10FPD900), Airport Electric Vehicles Battery (10FPD800) and so on.

(/ )

Supplier Homepage Product Standard battery LFP Series LFP12110 Stationary Sealed UPS Battery

LFP12110 Stationary Sealed UPS Battery

FOB Price: Get Latest Price
Min. Order: 10 Pieces
Production Capacity: 2000, 000kvah/ Year
Transport Package: Carton Packaging, 48PCS Per Pallet
Payment Terms: L/C, T/T

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: LFP12110(12V, 110Ah)
  • Usage: UPS, Electric Power, Lighting, Boat, Telecommunication
  • Discharge Rate: Medium Discharge Rate
  • Electrolyte: Acid
  • Rechargeable: Chargeable
  • UPS Battery: UPS Battery
  • Telecommunication Battery: Telecommunication Battery
  • UL,CE Vds Certified: UL,CE Vds Certified
  • Trademark: FirstPower
  • Origin: China
  • Type: Lead-Acid Batteries
  • Nominal Voltage: 12V
  • Shape: Square Battery
  • Installation: Fixed
  • Sealed and Maintenance-Free Operation: Sealed and Maintenance-Free Operation
  • Nonspillable Battery: Nonspillable Battery
  • AGM Separator Technology: AGM Separator Technology
  • BS Approval: BS Approval
  • Specification: UL, CE, ROHS VDS certified
  • HS Code: 8507200000
Product Description

LFP12110 Stationary Sealed UPS Battery  
FirstPower Technology Co., Ltd. was set up as a manufacturer of rechargeable batteries in 1993.
FirstPower brings you not only reliable battery and technology, but also excellent services and real value you shall expect and enjoy.We welcome orders with "FirstPower" brand; We are also flexible to accept orders on OEM basis. Contact us now! Your partnership with FirstPower will prove worthy of it.

International certifications:

  • ISO9001 approval, FN: Q3105105131
  • ISO14001 CTC04912E10302ROM
  • OHS MS18001 04912S10150ROM
  • UL approval, FN:MH28204
  • CE approval, FN:G2M20201-0102-E-16
  • KS approval, FN:KS C 8519
  • VDS approval
  • BS approval

General Features

  • Nonspillable
  • Sealed and Maintenance-free Operation
  • High Quality and High Reliability
  • Exceptional Deep Discharge Recovery
  • Low Self-discharge
  • Long Service Life
  • Solid Copper Terminals
  • Tank-formed Plates
  • Computer-aided Design and Manufacturing
 

Typical Applications

  • Telecommunication equipment
  • Electronic instruments
  • Fire alarm
  • Security devices
  • UPS power supply
  • Emergency lighting

    Specifications
Nominal Voltage12 V
Capacity
(25ºC)
10HR(10.8V) 110 Ah
5HR(10.5V)96.5Ah
1HR(9.60V)68.2Ah
DimensionLength281±2mm (11.06inch)
Width267±2mm (10.51inch)
Height207±2mm (8.15inch)
Total Height210±2mm (8.27inch)
Approx. Weight33kg (72.8lbs)±4%
Terminal typeT11
Internal resistance
(Fully charged, 25ºC)
Approx. 4mΩ
Capacity affected by temperature (10HR)40ºC102%
25ºC100%
0ºC85%
-15ºC65%
Self-discharge
(25ºC)
3 monthRemaining Capacity: 91%
6 monthRemaining Capacity: 82%
12 monthRemaining Capacity: 65%
Nominal operating temperature25ºC±3ºC(77ºF±5ºF)
Operating temperature rangeDischarge-15ºC~50ºC(5ºF~122ºF)
Charge-10ºC~50ºC(14ºF~122ºF)
Storage-20ºC~50ºC(-4ºF~122ºF)
Float charging voltage(25ºC)13.50 to 13.80V
Temperature compensation:
-18mV/ºC
Cyclic charging voltage(25ºC)14.50 to 14.90V
Temperature compensation:
-30mV/ºC
Maximum charging current33A
Terminal materialCopper
Maximum discharge current800A(5 sec.)
Designed floating life(20ºC) 12 years
Absorbent glass mat technology;
Recognized by UL & CE;
ABS container.

Dimensions

LFP12110 Stationary Sealed UPS Battery

Terminal :T11(M8)


Constant Current Discharge Characteristics (A, 25ºC)
F.V/TIME10min15min30min60min2h3h4h5h8h10h20h
9.60V23118211068.240.228.123.019.713.411.25.87
9.90V22417710867.239.927.922.919.513.411.25.86
10.2V21517110565.539.627.722.719.413.311.15.85
10.5V20616510264.139.127.522.619.313.211.15.82
10.8V19415698.262.238.126.721.918.712.811.05.78
Constant Power Discharge Characteristics (Watt, 25ºC)
F.V/TIME10min15min30min60min2h3h4h5h8h10h20h
9.60V24951993123477846533027123216013470.5
9.90V24201945121076646332826823116013370.4
10.2V23201873117374745932626722915813370.2
10.5V22211810114473245232326522815713269.7
10.8V20961714110271044031425722115213169.3
Note: The above characteristics data can be obtained within three charge/discharge cycles.