Gold Member Since 2016
Audited Supplier
Firstpower Tech. Co., Ltd.

Battery, EPS Battery, Telecommunication Battery manufacturer / supplier in China, offering Stationary Telecommunication Battery (CFP2500), DIN Standard Traction Battery (10FPD900), Airport Electric Vehicles Battery (10FPD800) and so on.

(/ )

Supplier Homepage Product Standard battery CFP Series Stationary Telecommunication Battery (CFP2500)

Stationary Telecommunication Battery (CFP2500)

FOB Price: Get Latest Price
Min. Order: 2 Pieces
Production Capacity: 2000, 000kvah/ Year
Transport Package: Carton Packaging, 51PCS Per Pallet
Payment Terms: L/C, T/T

Request a custom order and have something just for you!

Send Customized Request
Product Catalog
recommend products
7 Products
Content
Product Image
Product Name
FOB Price
Port
Basic Info
  • Model NO.: CFP2500(Stationary, 2V, 500Ah)
  • Usage: UPS, Electric Power, Lighting, Telecommunication
  • Discharge Rate: Medium Discharge Rate
  • Electrolyte: Acid
  • Rechargeable: Chargeable
  • UPS /EPS Battery: UPS/EPS Battery
  • Telecommunication Battery: Telecommunication Battery
  • Copper Core, Inserted Screw Terminal: Copper Core, Inserted Screw Terminal
  • Trademark: Firstpower
  • Origin: China
  • Type: Lead-Acid Batteries
  • Nominal Voltage: 2V
  • Shape: Square Battery
  • Installation: Fixed
  • Nonspillable Battery: Nonspillable Battery
  • Long Life-20 Years: Long Life-20 Years
  • Sealed and Maintenance-Free: Sealed and Maintenance-Free
  • Back up Battery: Back up Battery
  • Specification: UL, CE, ROHS certified
  • HS Code: 8507200000
Product Description

 CFP2500 Stationary Telecommunication Battery ( 2v,500Ah)
FirstPower Technology Co., Ltd. was set up as a manufacturer of rechargeable batteries in 1993.
FirstPower brings you not only reliable battery and technology, but also excellent services and real value you shall expect and enjoy.We welcome orders with "FirstPower" brand; We are also flexible to accept orders on OEM basis. Contact us now! Your partnership with FirstPower will prove worthy of it.

International certifications:

  • ISO9001 approval, FN: Q3105105131
  • ISO14001 CTC04912E10302ROM
  • OHS MS18001 04912S10150ROM
  • UL approval, FN:MH28204
  • CE approval, FN:G2M20201-0102-E-16
  • KS approval, FN:KS C 8519
  • VDS approval
  • BS approval


 CFP Series Battery General Features

  • Nonspillable
  • Sealed and Maintenance-free Operation
  • High Quality and High Reliability
  • Exceptional Deep Discharge Recovery
  • Low Self-discharge
  • Long Service Life
  • Solid Copper Terminals
  • Tank-formed Plates
  • Computer-aided Design and Manufacturing
  • UL, CE, VdS Approved

Typical Applications

  • Telecommunication equipment
  • Electronic instruments
  • Fire alarm
  • Security devices
  • UPS power supply
  • Emergency lighting

    Specifications
    Nominal Voltage2 V
    Capacity
    (25ºC)
    10HR(1.80V) 500 Ah
    3HR(1.75V)384Ah
    1HR(1.75V)282Ah
    DimensionLength241±2mm (9.49inch)
    Width171±2mm (6.73inch)
    Height330±2mm (12.99inch)
    Total Height365±2mm (14.37inch)
    Approx. Weight29.5kg (64.9lbs)±4%
    Terminal typeT10
    Internal resistance
    (Fully charged, 25ºC)
    Approx. 0.5mΩ
    Capacity affected by temperature (10HR)40ºC102%
    25ºC100%
    0ºC85%
    -15ºC65%
    Self-discharge
    (25ºC)
    3 monthRemaining Capacity: 91%
    6 monthRemaining Capacity: 82%
    12 monthRemaining Capacity: 65%
    Nominal operating temperature25ºC±3ºC(77ºF±5ºF)
    Operating temperature rangeDischarge-15ºC~50ºC(5ºF~122ºF)
    Charge-10ºC~50ºC(14ºF~122ºF)
    Storage-20ºC~50ºC(-4ºF~122ºF)
    Float charging voltage(25ºC)2.25 to 2.30V
    Temperature compensation:
    -3mV/ºC
    Cyclic charging voltage(25ºC)2.42 to 2.48V
    Temperature compensation:
    -5mV/ºC
    Maximum charging current100A
    Terminal materialCopper
    Maximum discharge current3500A(5 sec.)
    Designed floating life(20ºC)20 years
    Absorbent glass mat technology;
    Recognized by UL & CE;
    ABS container.


    Dimensions
    Stationary Telecommunication Battery (CFP2500)

    Terminal: M8

    Constant Current Discharge Characteristics (A, 25ºC)
    F.V/TIME30min60min2h3h4h5h6h8h10h20h24h
    1.60V45030018313010590.878.061.250.926.723.2
    1.65V44129618212910490.277.660.850.826.723.1
    1.70V42828818012810389.677.060.450.726.623.0
    1.75V41728217712810389.076.560.050.426.422.9
    1.80V40227417312499.486.374.258.250.026.322.8
    Constant Power Discharge Characteristics (Watt, 25ºC)
    F.V/TIME30min60min2h3h4h5h6h8h10h20h24h
    1.60V84257035325520517915412210153.446.6
    1.65V82556135125320417815312110153.346.5
    1.70V79954734725220217715212010153.246.3
    1.75V78053634225020117515111910052.946.0
    1.80V75152033424219517014611699.552.545.7
    Note: The above characteristics data can be obtained within three charge/discharge cycles.

    Stationary Telecommunication Battery (CFP2500)
    Stationary Telecommunication Battery (CFP2500)
    Send your message to this supplier
    Avatar
    Mr. Jason
    *From:
    To: Mr. Jason
    *Message:

    Enter between 20 to 4,000 characters.

    This is not what you are looking for? Post a Sourcing Request Now