Gold Member Since 2016
Audited Supplier
Firstpower Tech. Co., Ltd.

Battery, UPS Battery, Sealed Lead Acid Battery manufacturer / supplier in China, offering Fire Alarm Battery (LFP636), DIN Standard Traction Battery (10FPD900), Airport Electric Vehicles Battery (10FPD800) and so on.

(/ )

Supplier Homepage Product Standard battery LFP Series Fire Alarm Battery (LFP636)

Fire Alarm Battery (LFP636)

FOB Price: Get Latest Price
Min. Order: 10 Pieces
Production Capacity: 2000, 000kvah/ Year
Transport Package: Carton Packaging, 250PCS Per Pallet
Payment Terms: L/C, T/T

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: LFP636(6V, 36Ah)
  • Usage: UPS, Electric Power, Boat, Telecommunication
  • Discharge Rate: Medium Discharge Rate
  • Electrolyte: Acid
  • Rechargeable: Chargeable
  • Nonspillable Battery: Nonspillable Battery
  • Back up Battery: Back up Battery
  • Security Devices Battery: Security Devices Battery
  • Fire Alarm Battery: Fire Alarm Battery
  • Specification: UL, CE, ROHS certified
  • HS Code: 8507200000
  • Type: Lead-Acid Batteries
  • Nominal Voltage: 6V
  • Shape: Square Battery
  • Installation: Fixed
  • Sealed and Maintenance-Free Operation: Sealed and Maintenance-Free Operation
  • Low Self-Discharge: Low Self-Discharge
  • UPS Battery: UPS Battery
  • AGM Separator Technology: AGM Separator Technology
  • Trademark: FirstPower
  • Origin: China
Product Description

Fire alarm battery (LFP636)

FirstPower Technology Co., Ltd. was set up as a manufacturer of rechargeable batteries in 1993.
FirstPower brings you not only reliable battery and technology, but also excellent services and real value you shall expect and enjoy.xcxzWe welcome orders with "FirstPower" brand; We are also flexible to accept orders on OEM basis. Contact us now! Your partnership with FirstPower will prove worthy of it.

International certifications:

  • ISO9001 approval, FN: Q3105105131
  • ISO14001 CTC04912E10302ROM
  • OHS MS18001 04912S10150ROM
  • UL approval, FN:MH28204
  • CE approval, FN:G2M20201-0102-E-16
  • KS approval, FN:KS C 8519
  • VDS approval
  • BS approval
 

General Features

  • Nonspillable
  • Sealed and Maintenance-free Operation
  • High Quality and High Reliability
  • Exceptional Deep Discharge Recovery
  • Low Self-discharge
  • Long Service Life
  • Solid Copper Terminals
  • Tank-formed Plates
  • Computer-aided Design and Manufacturing
 

Typical Applications

  • Telecommunication equipment
  • Electronic instruments
  • Fire alarm
  • Security devices
  • UPS power supply
  • Emergency lighting

Specifications
Nominal Voltage6 V
Capacity
(25ºC)
10HR(5.40V) 36 Ah
 5HR(5.25V)31.5Ah
 1HR(4.80V)22.3Ah
DimensionLength162±2mm (6.38inch)
 Width88±1mm (3.46inch)
 Height164±2mm (6.46inch)
 Total Height170±2mm (6.69inch)
Approx. Weight5.5kg (12.1lbs)±4%
Terminal typeT2
Internal resistance
(Fully charged, 25ºC)
Approx. 4.5mΩ
Capacity affected by temperature (10HR)40ºC102%
 25ºC100%
 0ºC85%
 -15ºC65%
Self-discharge
(25ºC)
3 monthRemaining Capacity: 91%
 6 monthRemaining Capacity: 82%
 12 monthRemaining Capacity: 65%
Nominal operating temperature25ºC±3ºC(77ºF±5ºF)
Operating temperature rangeDischarge-15ºC~50ºC(5ºF~122ºF)
 Charge-10ºC~50ºC(14ºF~122ºF)
 Storage-20ºC~50ºC(-4ºF~122ºF)
Float charging voltage(25ºC)6.75 to 6.90V
Temperature compensation:
-9mV/ºC
Cyclic charging voltage(25ºC)7.25 to 7.45V
Temperature compensation:
-15mV/ºC
Maximum charging current10.8A
Terminal materialCopper
Maximum discharge current200A(5 sec.)
Designed floating life(20ºC)12 years

Absorbent glass mat technology;
Recognized by UL /CE & Vds;
ABS container.

   Dimensions
Fire Alarm Battery (LFP636)

 Terminal :T2


Constant Current Discharge Characteristics (A, 25ºC)
F.V/TIME15min30min60min2h3h4h5h6h8h10h20h
4.80V----22.3 13.2 9.18 7.53 6.43 5.62 4.41 3.66 1.92
4.95V----22.0 13.1 9.13 7.48 6.39 5.59 4.38 3.66 1.92
5.10V----21.4 13.0 9.06 7.43 6.34 5.55 4.35 3.65 1.91
5.25V----21.0 12.8 9.00 7.38 6.30 5.51 4.32 3.63 1.90
5.40V----20.4 12.4 8.73 7.16 6.11 5.34 4.19 3.60 1.89
Constant Power Discharge Characteristics (Watt, 25ºC) 
F.V/TIME15min30min60min2h3h4h5h6h8h10h20h
4.80V----127 76.2 54.0 44.3 38.0 33.2 26.2 21.9 11.5
4.95V----125 75.7 53.7 44.0 37.8 33.0 26.0 21.8 11.5
5.10V----122 75.0 53.3 43.7 37.5 32.8 25.8 21.8 11.5
5.25V----120 73.9 52.9 43.4 37.2 32.6 25.7 21.6 11.4
5.40V----116 72.0 51.3 42.1 36.1 31.6 24.9 21.5 11.3
Note: The above characteristics data can be obtained within three charge/discharge cycles.


Fire Alarm Battery (LFP636)

 
Send your message to this supplier
Avatar
Mr. Jason
*From:
To: Mr. Jason
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now